Air-insulated, Indoor Metal-clad VCB Switchboards

SRIWIN ELECTRIC, an ISO 9001-2015 certified company, offers Air-insulated, Indoor Metal-clad VCB Switchboards in 12kV/24kV/36kV Voltage Ratings. These switchboards incorporate highly reliable Vacuum Circuit Breakers as Switching Medium and are offered either as stand-alone units or as Line-up Switchboards.

12kV Indoor ICOG VCB Switchboard

12kV Indoor ICOG VCB Switchboard

12kV Indoor ICOG VCB Switchboard

12kV Indoor VCB Switchboard Line-up

12kV Indoor VCB Switchboard Line-up

12kV Indoor VCB Switchboard Line-up

24kV Indoor ICOG VCB Switchboard

24kV Indoor ICOG VCB Switchboard

24kV Indoor ICOG VCB Switchboard

24kV Indoor VCB Switchboard Line-up

24kV Indoor VCB Switchboard Line-up

24kV Indoor VCB Switchboard Line-up

  • Available in 12kV/24kV/36kV
  • Available up to 3150A, 40kA
  • Stand-alone Switchboard (ICOG)
  • Cable-in-Cable-out Switchboard (CICO)
  • Line-up Switchboard
  • Draw-out Design
  • Roll-on-floor Type
  • Cassette Type (Optional)
  • Fixed Type (Optional)
  • Fully Compartmentalised
  • Spring Charged Mechanism
  • Magnetic Actuator Mechanism (Optional)
  • Adequate Termination Space
  • Flexible LV Control & Protection
  • Flexible Metering Options
  • Interlocks as per IS/IEC Standards
  • Degree of Protection: IP 4X (Indoor)
  • SCADA/DMS/EMS/BMS/SAS compatible
  • Various Optional Accessories
  • Type Tested as per IS/IEC Standards
  • VCB cannot be closed in any intermediate position, other than in Service Position or in Test/Isolated Position
  • The VCB Truck cannot be racked IN or raked OUT, when the VCB is ON
  • The VCB Truck cannot be racked IN, unless the control plug is inserted in its socket
  • The control plug cannot be removed from its socket in Service position
  • Pad locking facility for the front door
  • Door Interlock–prevents opening of the front door, while the VCB is ON & prevents closing of the VCB, when the front door is open (Optional)
  • Manual/Electrical Stored Energy Spring Charged Mechanism
  • Magnetic Actuator Mechanism (Optional)
  • Suitable for rapid auto reclosing
  • In-built anti-pumping
  • Simple
  • Robust
  • Long Life
  • Low Maintenance
  • Tested for M2 Class (10, 000 Operations)
  • Integral Earth Switch
  • Earthing Truck–cable Side
  • Earthing Truck–bus Side
  • Fixed PT or Draw-out PT
  • Rear mounted Draw-out PT
  • Top mounted Draw-out PT
  • Sealable CT/PT Chamber
  • Sealable Metering Chamber
  • Tariff Metering
  • VCB handling Trolley (for Cassette Type VCBs)
  • Metallic Safety Shutters
  • Live Line Indicators
  • Rear (Cable Chamber) Cover Interlocks
  • Bus Chamber Cover Interlocks
  • Remote Control Panel
  • Remote Annunciation Panel
  • Utilities
  • Incomers
  • Bus Couplers
  • Outgoing Feeders
  • Residential Complex
  • Commercial Complex
  • Shopping Malls
  • Hotels
  • Hospitals
  • Industries
  • Power Plants
  • Solar Power Plants
  • Unitised Sub Stations
  • EB Metering Panels
  • Transformers
  • Motors
  • Reactors
  • Capacitors
  • Cable Feeders
  • Overhead Feeders
  • Line Feeders

Guaranteed Technical Particulars

PARAMETER 12kV 12kV 24kV 36kV
Rated Voltage (kV) 12 12 24 36
Rated Frequency (Hz.) 50/60 50/60 50/60 50/60
Rated Insulation Level (kV) 12/28/75 12/28/75 24/50/125 36/70/170
Rated Current-Busbar (A) 800
1250
1600
2000
3150
800
1250
1600
2000
800
1250
1600
2000
2500
Rated Current-Breaker (A) 800
1250
1600
2000
3150
800
1250
1600
2000
800
1250
1600
2000
2500
Rated Short Circuit Breaking Capacity (kA) 25
31.5
40
25
31.5
40
25 25
31.5
Rated Short Circuit Making Capacity (kAp) 62.5
78.75
100
62.5
78.75
100
62.5 62.5
78.75
Rated Short Time Withstand Current (kA) 25
31.5
40
25
31.5
40
25 25
31.5
Rated Short Time Withstand Duration (Sec.) 3 3 3 3
Rated Operating Sequence O-300ms-CO-3min.-CO
Spring Charge Motor Voltage 230V AC (85% to 110%)
Spring Charging Time 12 sec.@ rated motor voltage
Rated Closing Coil Voltage 24/30/48/110/220V DC (85% to 110%)
Rated Trip Coil Voltage 24/30/48/110/220V DC (70% to 110%)
Closing Time <65ms at rated close coil voltage
Tripping Time <45ms at rated trip coil voltage
Mechanical Life 10000 Operations
Electrical Life at Rated Current 20000 Operations
Electrical Life at Rated Short Circuit Breaking Current 100 Operations
Aux. Contact 6 N.O. + 6 N.C.
Degree of Protection (Enclosure) IP4X
Standard IS/IEC 62271-100/200